Refrigerant Charge Calculator
Calculate the required refrigerant charge for HVAC/refrigeration systems based on system capacity, line set length, and refrigerant type.
Formulas Used
Tube Internal Volume:
ID = OD − 2 × wall_thickness
V = π × (ID/2)² × L
where L = line length, ID = internal diameter (ACR Type L copper)
Method 1 — Volume-Based Charge:
m_liquid = V_liquid × ρ_liquid
m_vapor = V_suction × ρ_vapor
Total Charge = (m_liquid + m_vapor) × 16 [oz]
where ρ_liquid = liquid refrigerant density at ~100°F (lb/ft³), ρ_vapor = vapor density at ~45°F saturated suction (lb/ft³)
Method 2 — Manufacturer Adder Method (ACCA/ASHRAE Standard):
Total Charge = Q_factory + (L_liquid − L_base) × k_liquid + L_suction × k_suction
where Q_factory = nameplate factory charge (oz), L_base = factory-rated line set length (ft), k_liquid = liquid line oz/ft adder, k_suction = suction line oz/ft adder