HVAC System BTU Sizing Calculator

Estimate the heating and cooling BTU capacity required for your space using the Manual J load calculation methodology.

Room Dimensions

Climate & Exposure

Insulation & Construction

Formulas Used

Cooling / Heating Conduction Load (BTU/hr):

Q_cond = A × U × ΔT

Where A = surface area (ft²), U = overall heat transfer coefficient (BTU/hr·ft²·°F), ΔT = design temperature difference (°F).

Solar Heat Gain (cooling only):

Q_solar = A_window × SHGC × I_solar × SunMultiplier

Where SHGC = Solar Heat Gain Coefficient, I_solar = 150 BTU/hr·ft² (average peak irradiance).

Infiltration Load (BTU/hr):

Q_inf = Volume × ACH × 0.018 × ΔT

Where 0.018 BTU/ft³·°F is the volumetric heat capacity of air at standard conditions, ACH = air changes per hour.

Internal Gains (cooling):

Q_internal = (Occupants × 250) + Kitchen + (Floor Area × 3)

250 BTU/hr per person (sensible), 1,200 BTU/hr for kitchen, 3 BTU/hr·ft² for lighting.

Total Cooling Load:

Q_cool = (Q_cond + Q_solar + Q_inf + Q_internal) × ClimateFactor × StoryFactor

Tonnage:

Tons = BTU/hr ÷ 12,000

1 ton of refrigeration = 12,000 BTU/hr. Equipment is rounded up to the nearest 0.5 ton.

Assumptions & References

  • Based on ACCA Manual J (8th Edition) simplified residential load calculation methodology.

In the network