HVAC System BTU Sizing Calculator
Estimate the heating and cooling BTU capacity required for your space using the Manual J load calculation methodology.
Room Dimensions
Climate & Exposure
Insulation & Construction
Formulas Used
Cooling / Heating Conduction Load (BTU/hr):
Q_cond = A × U × ΔT
Where A = surface area (ft²), U = overall heat transfer coefficient (BTU/hr·ft²·°F), ΔT = design temperature difference (°F).
Solar Heat Gain (cooling only):
Q_solar = A_window × SHGC × I_solar × SunMultiplier
Where SHGC = Solar Heat Gain Coefficient, I_solar = 150 BTU/hr·ft² (average peak irradiance).
Infiltration Load (BTU/hr):
Q_inf = Volume × ACH × 0.018 × ΔT
Where 0.018 BTU/ft³·°F is the volumetric heat capacity of air at standard conditions, ACH = air changes per hour.
Internal Gains (cooling):
Q_internal = (Occupants × 250) + Kitchen + (Floor Area × 3)
250 BTU/hr per person (sensible), 1,200 BTU/hr for kitchen, 3 BTU/hr·ft² for lighting.
Total Cooling Load:
Q_cool = (Q_cond + Q_solar + Q_inf + Q_internal) × ClimateFactor × StoryFactor
Tonnage:
Tons = BTU/hr ÷ 12,000
1 ton of refrigeration = 12,000 BTU/hr. Equipment is rounded up to the nearest 0.5 ton.
Assumptions & References
- Based on ACCA Manual J (8th Edition) simplified residential load calculation methodology.